Climate Change Levy (CCL) Reconciliation

CCL Reconciliation

As we come to the end of the CHPQA submission process, many CHP operators will have received their CHPQA certificates validating their performance for the calendar year 2014.

With receipt of your CHPQA certificate you must now undertake CCL Reconciliation for HM Revenue & Customs (HMRC). This is a mandatory requirement and must be carried out sixty (60) days from date of certification, otherwise penalties can be imposed.

HMRC guidance states:

“On receipt of a new CHPQA certificate, and following its submission to BEIS for Secretary of State Certificate purposes, you must review your PP11 Supplier Certificate and reconcile the amount of CCL relief claimed on taxable commodities used as fuel inputs against the actual performance of the station over the same period.”

CCL Reconciliation for CHP operators falls into two categories: Gas Consumed by the CHP unit and Electricity Generated by the CHP unit.

Gas Consumed by the CHP unit

Your CCL exemption rate is based on the ratio between your Qualifying Fuel Input (QFI) against your total gas input. Your QFI is shown on your CHPQA certificate; thus if your:

  • QFI = 1,616 MWh
  • Total Gas Input = 3,232 MWh

Then your CCL exemption = 1,616 / 3,232 = 50%

This calculation assumes no other exemptions are applicable (e.g. Climate Change Agreements) and is calculated using HMRC form PP10 (Climate Change Levy Relief supporting analysis), a copy of which you must send to HMRC.

Once the exemption rate has been calculated this is transposed to the PP11 Supplier Certificate and sent to your gas supplier to be applied to the appropriate account.

So your CCL exemption rate going forward is based on the previous year’s CHP validated QFI and total gas consumption. Simply put your CCL exemption in 2014 was based upon the validated QFI and total gas consumption data for 2013; likewise your CCL exemption in 2015 will be based on the validated QFI and total gas consumption data for 2014.

This is where CCL reconciliation comes in; you have to review your actual performance and CCL exemption in 2014 against the predicted exemption rate (based on the 2013 figures) for the year.

So if in 2013 your PP10 calculation showed an exemption rate of say 60% for 2014, but upon receipt of your CHPQA certificate for the 2014 calendar year your calculation showed an exemption of 50%; then there has been an underpayment of CCL. You were claiming a 60% exemption in 2014 but were only entitled to a 50% exemption and a repayment to HMRC of the difference is required.

Worked Example

The 2013 QFI and operational data gave the Leisure Centre a 58% exemption rate; however upon receipt of the new CHPQA certificate the QFI/Total Gas Consumption calculation showed an exemption of only 52.73%. So reconciliation must be carried out to determine the repayment to HMRC:

CCL Reconciliation Report: Example Leisure Centre
Year: 2014
Site Number: 37
MPR Number(s): 123456789

Period Covered Total Site Gas (kWh) Billed CCL Discount (%) CCL Payment Billed (£) CCL Discount (%) CCL Payment Due (£) Reconciliation Payment (£)
January 291,427 58.00% £222.77 52.73% £250.72 £27.95
February 360,431 58.00% £275.51 52.73% £310.08 £34.57
March 291,426 58.00% £222.77 52.73% £250.72 £27.95
April 247,659 58.00% £195.55 52.73% £220.09 £24.54
May 250,295 58.00% £197.63 52.73% £222.43 £24.80
June 216,096 58.00% £170.63 52.73% £192.04 £21.41
July 187,713 58.00% £148.22 52.73% £166.82 £18.60
September 172,807 58.00% £136.45 52.73% £153.57 £17.12
October 269,128 58.00% £212.50 52.73% £239.17 £26.67
November 266,056 58.00% £210.08 52.73% £236.44 £26.36
December 286,141 58.00% £225.94 52.73% £254.29 £28.35
Totals 3,064,654   £2,396.09   £2,696.73 £300.64

In this case a repayment of £300.64 is due and payment should be made using a self-declaration to HMRC for the amount shown.

Electricity Generated by the CHP unit

CCL reconciliation on CHP electricity is much easier to calculate, it is based on the difference between the schemes Total Power Output (TPO) and the Qualifying Power Output (QPO); both of these are shown on your CHPQA certificate.

The amount owed is calculated by subtracting the QPO from the TPO and multiplying the difference by the relevant rate of CCL for electricity.

Worked Example

From the 2014 CHPQA certificate we have the following values:

  • TPO = 485 MWh
  • QPO = 400 MWh

Therefore the amount owed would be:

  • 485 – 400 = 85 MWh x 1,000 = 85,000 kWh x £0.00541 = £459.85

As there is no means to make a self-declaration for CCL reconciliation on electricity, the CHP operator would be required to register to pay CCL using HMRC form CCL1 and thereafter complete quarterly returns.

For more information on CCL or CHPQA please visit the following pages:

For further information on CCL Reconciliation and other services offered, please contact us either by email to info@2ea.co.uk or by calling 01293 521 350.


2EA® are registered Low Carbon Energy Assessors, Consultants & ESOS Lead Assessors offering both energy management and reduction services ranging from Energy Saving Opportunity Scheme (ESOS), Display Energy Certificates (DEC) to Carbon Reduction Commitment (CRC) consultancy.

    Contact Us